| Manufacturer | AMPHENOL ADVANCED SENSORS |
|---|---|
| Manufacturer Part No | T8031Copy |
| Manufacturer Standard Lead Time | 6 weeks |
| Order Code | 3928607 |
| Product Range | Ventostat Series |
| Your Part Number | |
| Technical Datasheet |
10 In Stock
Need more?
10 Delivery in 3-4 Business Days(UK stock)
| Quantity | Price (inc GST) |
|---|---|
| 1+ | S$227.190 (S$247.6371) |
Price for:Each
Minimum: 1
Multiple: 1
S$227.19 (S$247.64 inc GST)
Line Note
Added to your Order Confirmation, Invoice, and Dispatch note for this order only.
Product Information
| Manufacturer | AMPHENOL ADVANCED SENSORS |
|---|---|
| Manufacturer Part No | T8031Copy |
| Manufacturer Standard Lead Time | 6 weeks |
| Order Code | 3928607 |
| Product Range | Ventostat Series |
| Technical Datasheet | |
| Gas Type | Carbon Dioxide |
| Particle Count Max | 2000ppm |
| Accuracy % | 3% |
| Sampling Method | Diffusion |
| Product Range | Ventostat Series |
| SVHC | No SVHC (07-Jul-2017) |
Product Overview
T8031 Telaire Ventostat T8031 CO2 duct mount transmitter is the smallest package available designed to be installed in HVAC return air ducts. It is designed for indoor air quality and energy conservation applications, offering accuracy and versatility at an affordable price. This exceptional product line touts an unobtrusive form factor that is easy to install, simple to use, and remains accurate over the expected life of the device using Telaire’s patented ABC Logic™ (Automatic Background Calibration) technology. Application includes HVAC return air ducts.
- One of the smallest in-duct CO2 transmitters on the market
- Simple installation (mounting hardware and instructions included)
- Ideally suited for OEM MFRs that must accommodate smaller <lt/> 15.2cm HVAC return air ducts
- Offers standard 0-10V output, response time is 3m typical for a 90% step change at low duct speeds
- Patented absorption infrared/gas sensing engine provides high accuracy in compact, low-cost package
- Patented ABC Logic™ self-calibration system eliminates need for manual calibration
- Measurement range from 0-2000ppm factory calibrated
- Temp dependence 0.2% of full scale per °C
- Operating conditions temperature range from 0°C to 50°C
- Duct air velocity of 0 to 1500ft/min (0 to 450meter/min)
Technical Specifications
| Gas Type | Carbon Dioxide |
|---|---|
| Accuracy % | 3% |
| Product Range | Ventostat Series |
| Particle Count Max | 2000ppm |
|---|---|
| Sampling Method | Diffusion |
| SVHC | No SVHC (07-Jul-2017) |
Technical Docs (1)
Legislation and Environmental
| Country of Origin: Country in which last significant manufacturing process was carried outCountry of Origin: | Mexico Country in which last significant manufacturing process was carried out |
|---|---|
| Tariff No: | 90271010 |
| US ECCN: | EAR99 |
| EU ECCN: | NLR |
| RoHS Compliant: | Yes RoHS |
| RoHS Phthalates Compliant: | Yes RoHS |
| SVHC: | No SVHC (07-Jul-2017) |
| Download Product Compliance Certificate | Product Compliance Certificate |
| Weight (kg): | .074389 |